12 AWG 600V Tip TC-ER Oklopljeni kontrolni kabel PVC Najlon PVC

12 AWG 600V Tip TC-ER Oklopljeni kontrolni kabel PVC Najlon PVC
Details:
·Jakna od PVC-a
·Potpuno žareni goli bakar klase B
·Prekriveno polivinil kloridom (PVC).
· Punilo (po potrebi)
·Oznaka napona: 600V
· Temperatura: Ocijenjena na 90 stupnjeva mokro ili suho
· Raspon veličina: Dostupan u veličinama od 18 do 10 AWG
·Standard: UL83/UL1277
·Dostupan u 2 do 37 vodiča
·Boja: Prema ICEA S-58-679 Metoda 1, Tablica E-2; dostupne dodatne mogućnosti kodiranja boja
Send Inquiry
Download
Opis
Tehnički parametri
Certifikacija

600V control cable for raceway

PROIZVOD PRAVI SNIMAK

 

TC-ER control cable for wireway
TC-ER control cable for wireway
600V control cable for wireway

VNTC tray cable for trough

12 AWG oklopljeni PVC najlonski PVC kabel klase 1 Div 2 VNTC nosač
Ovaj12 AWG 600V tip TC-ER oklopljeni upravljački kabelje kvalificiranClass 1 Div 2 VNTC nosač kabela, standardno certificiranUL 1277 nosač kabela 600V, izgrađen saASTM B8 višežilni kabel s bakrenom policivodiče i odgovarajuće robusneTC-ER upravljački kabel za kanal. S tro-slojnom PVC/najlonskom/PVC THHN izolacijom, potpunom aluminijskom zaštitom od Mylar folije i anti{2}}crnim PVC omotačem, prilagođava se kabelskim kanalima, policama, cjevovodima, vanjskim izloženim i izravnim ukopanim ožičenjima u opasnim industrijskim zonama, ocijenjeno 90 stupnjeva mokro/suho uz potpunu usklađenost sa sjevernoameričkim električnim standardom.
SPECIFIKACIJE PROIZVODA

 

THHN PVC tray cable for wireway

Opis proizvoda

 

PVC/najlon/PVC (THHN/THWN-2), 600 V upravljački, tip TC-ER i kablovi za izravno ukopavanje sastoje se od potpuno žarenih golih bakrenih vodiča klase B, prekrivenih polivinil kloridom (PVC) otpornim na ulje i plin i prozirnom najlonskom izolacijom, neoklopljenom ili oklopljenom i crnim PVC omotačem. Ovi se kabeli koriste u industrijskim strujnim ili kontrolnim krugovima stanica.

Prijave

 
  • U cjevovodima, kanalima, slobodnim zrakom, kanalima i izravnim ukopima, primarne instalacije uključuju police za kabele i vanjske lokacije

  • Na mokrim ili suhim mjestima

  • Odobreno za Klasu I, Div. 2 industrijska opasna mjesta prema NEC-u

  • Dopušteno za izloženi rad (ER) koji se koristi u skladu s NEC za 3 ili više vodiča; dva vodiča bez žice za uzemljenje su samo tipa TC

Značajke

 
  • Ocijenjeno na 90 stupnjeva mokro ili suho
  • Ripcord (po potrebi)
  • Izvrsna otpornost na sunčevu svjetlost
  • Zadovoljava test hladnog savijanja na -25 stupnjeva
TEHNIČKI PODACI

Dirigent grof

Dostupan u 2 do 37 vodiča

Dirigent

Potpuno žareni goli bakar klase B

Mjerne veličine

Dostupan u veličinama od 18 do 10 AWG

Izolacija

Pokriven polivinil kloridom (PVC).
• 14 AWG i veći su tip THHN/THWN-2
Kodiranje boja Prema ICEA S-58-679 Metoda 1, Tablica E-2; dostupne dodatne mogućnosti kodiranja boja
Punila Ne-higroskopna punila, ako je potrebno za postizanje kružnog presjeka
Štit (opcionalno) Cjelokupna aluminijska poliesterska (mylar) folija u kontaktu s 20 AWG užetanom pokositrenom bakrenom odvodnom žicom
Jakna Polivinil klorid (PVC)

Označavanje jakne

Veličine vodiča 18 AWG – 16 AWG: 00000 FT VEĆI ŽIČANI KABEL XXAWG XX/C PVC/NYLON PVC JKT (ili OS) 600V 90C MOKRO ILI SUHO TIP TC (ili -ER) (UL) SUN RES DIR BUR FT4/IEEE1202 MADE IN CHINA MMDDYYYY Veličine vodiča 14 AWG – 10 AWG: 00000 FT VEĆI ŽIČANI KABEL XXAWG XX/C THHN/THWN-2 PVC JKT (ili OS) 600V 90C MOKRO ILI SUHO TIP TC (ili -ER) (UL) SUN RES DIR BUR FT4/IEEE1202 PROIZVEDENO U KINI MMDDGGGG

Pakiranje

Ne-povratni drveni koluti u raznim duljinama i dimenzijama

Sukladnost izvedbe

ASTM B8, ASTM B33

UL 83

UL 1277

UL 1685 (ispitivanje izloženosti plamenu)

ANSI/NEMA WC 70/ICEA S-95-658

ANSI/NEMA WC 57/ICEA S-73-532

NEC

Ostale usklađenosti

EPA 40 CFR, dio 261

OSHA

RoHS-sukladan/RoHS 2-sukladan

Sukladno-REACH

Bez zaštite

Dirigent grof Veličina vodiča AWG Debljina izolacije
u (mm)
Debljina jakne
u (mm)
cca. Ukupni promjer
u (mm)
cca. Neto težina
lbs/kft (kg/km)

2

18 0.020(0.51) 0.045(1.14) 0.28(7.1) 40(56)
3 18 0.020(0.51) 0.045(1.14) 0.29(7.5 50 (69)
4 18 0.020(0.51) 0.045(1.14) 0.32(8.0) 60(84)
5 18 0.020(0.51) 0.045(1.14) 0.34(8.7) 70(99)
7 18 0.020(0.51) 0.045(1.14) 0.37(9.4) 85(126)
9 18 0.020(0.51) 0.045(1.14) 0.43(10.9) 110(158)
12 18 0.020(0.51) 0.045(1.14) 0.47(12.0) 135(199)
19 18 0.020(0.51) 0.045(1.14) 0.55(14.0) 205(298)
25 18 0.020(0.51) 0.060(1.52) 0.67(17.1) 280(414)
37 18 0.020(0.51) 0.060(1.52) 0.76(19.4) 390(573)
2 16 0.020(0.51) 0.045(1.14) 0.30(7.7) 50 (69)
3 16 0.020(0.51) 0.045(1.14) 0.32(8.1) 60(88)
4 16 0.020(0.51) 0.045(1.14) 0.35(8.8) 75(109)
5 16 0.020(0.51) 0.045(1.14) 0.37(9.5) 90 (130)
7 16 0.020(0.51) 0.045(1.14) 0.40(10.3) 115(168)
9 16 0.020(0.51) 0.045(1.14) 0.47(12.0) 145(211)
12 16 0.020(0.51) 0.045(1.14) 0.52(13.3) 185(269)
16 16 0.020(0.51) 0.060(1.52) 0.61(15.6) 255(378)
19 16 0.020(0.51) 0.060(1.52) 0.64(16.4) 295(435)
25 16 0.020(0.51) 0.060(1.52) 0.75(18.9) 380(560)
30 16 0.020(0.51) 0.060(1.52) 0.79(20.0) 440(653)
37 16 0.020(0.51) 0.060(1.52) 0.85(21.5) 530(784)
2 14 0.020(0.51) 0.045(1.14) 0.33(8.4) 60(88)
3 14 0.020(0.51) 0.045(1.14) 0.35(8.8) 80(115)
4 14 0.020(0.51) 0.045(1.14) 0.38(9.6) 100(143)
5 14 0.020(0.51) 0.045(1.14) 0.41(10.4) 120(172)
7 14 0.020(0.51) 0.045(1.14) 0.45(11.3) 155(226)
9 14 0.020(0.51) 0.045(1.14) 0.52(13.2) 195(285)
12 14 0.020(0.51) 0.060(1.52) 0.61(15.5) 265(393)
19 14 0.020(0.51) 0.060(1.52) 0.71(18.1) 400(591)
25 14 0.020(0.51) 0.060(1.52) 0.83(21.0)   515(763)
30 14 0.020(0.51) 0.060(1.52) 0.87(22.2)    605(895)
37 14 0.020(0.51) 0.080(2.03) 0.98(25.0) 765(1,138)
2 12 0.020(0.51) 0.045(1.14) 0.37(9.3) 80(117)
3 12 0.020(0.51) 0.045(1.14) 0.39(9.8) 110(157)
4 12 0.020(0.51) 0.045(1.14) 0.42(10.7) 135(198)
5 12 0.020(0.51) 0.045(1.14) 0.46(11.7) 165(240)
7 12 0.020(0.51) 0.045(1.14) 0.50(12.7) 215(318)
9 12 0.020(0.51) 0.060(1.52) 0.62(15.7) 290(431)
12 12 0.020(0.51) 0.060(1.52) 0.69(17.4) 375(553)
19 12 0.020(0.51) 0.060(1.52) 0.80(20.3) 565(840)
25 12 0.020(0.51) 0.080(2.03) 0.98(24.8) 775(1,147)
30 12 0.020(0.51) 0.080(2.03) 1.03(26.2) 905(1,344)
37 12 0.020(0.51) 0.080(2.03) 1.11(28.2) 1,090(1,622)
2 10 0.025(0.64) 0.025(0.64) 0.43(11.0) 115(169)
3 10 0.025(0.64) 0.025(0.64) 0.46(11.7) 160(231)
4 10 0.025(0.64) 0.025(0.64) 0.50(12.8) 200(295)
5 10 0.025(0.64) 0.025(0.64) 0.58(14.8) 260(385)
7 10 0.025(0.64) 0.025(0.64) 0.63(16.1) 345(511)
9 10 0.025(0.64) 0.025(0.64) 0.74(18.9) 435(647)
12 10 0.025(0.64) 0.025(0.64) 0.83(21.0) 565(836)

 

Sveukupno zaštićeno

Broj parova Veličina vodiča AWG Debljina izolacije
u (mm)
Debljina jakne
u (mm)
cca. Ukupni promjer
u (mm)
cca. Neto težina
lbs/kft (kg/km)

2

18 0.020(0.51) 0.045(1.14) 0.28(7.2) 45(62)
3 18 0.020(0.51) 0.045(1.14) 0.30(7.5) 55(76)
4 18 0.020(0.51) 0.045(1.14) 0.32(8.1) 65(91)
5 18 0.020(0.51) 0.045(1.14) 0.34(8.8) 75(106)
7 18 0.020(0.51) 0.045(1.14) 0.37(9.4) 90(133)
9 18 0.020(0.51) 0.045(1.14) 0.43(10.9) 115(165)
12 18 0.020(0.51) 0.045(1.14) 0.48(12.1) 140(207)
19 18 0.020(0.51) 0.045(1.14) 0.56(14.1) 210(306) 
25 18 0.020(0.51) 0.060(1.52) 0.68(17.2) 285(423)
37 18 0.020(0.51) 0.060(1.52) 0.77(19.5) 395(583)
2 16 0.020(0.51) 0.045(1.14) 0.31(7.8) 55 (76)
3 16 0.020(0.51) 0.045(1.14) 0.32(8.2) 65(95)
4 16 0.020(0.51) 0.045(1.14) 0.35(8.9) 80(116)
5 16 0.020(0.51) 0.045(1.14) 0.38(9.6) 95(137)
7 16 0.020(0.51) 0.045(1.14) 0.41(10.4) 120(175)
9 16 0.020(0.51) 0.045(1.14) 0.47(12.1) 150(219)
12 16 0.020(0.51) 0.045(1.14) 0.53(13.4) 190(277)
16 16 0.020(0.51) 0.060(1.52) 0.62(15.7) 265(387)
19 16 0.020(0.51) 0.060(1.52) 0.65(16.4) 300(444)
25 16 0.020(0.51) 0.060(1.52) 0.75(19.0) 385(569)
30 16 0.020(0.51) 0.060(1.52) 0.79(20.1) 450(663)
37 16 0.020(0.51) 0.060(1.52) 0.85(21.6) 535(794)
2 14 0.020(0.51) 0.045(1.14) 0.33(8.4) 65(94)
3 14 0.020(0.51) 0.045(1.14) 0.35(8.9) 65(95)
4 14 0.020(0.51) 0.045(1.14) 0.38(9.6) 85(121)
5 14 0.020(0.51) 0.045(1.14) 0.41(10.4) 105(150)
7 14 0.020(0.51) 0.045(1.14) 0.44(11.3) 125(179)
9 14 0.020(0.51) 0.045(1.14) 0.52(13.2) 160(232)
12 14 0.020(0.51) 0.060(1.52) 0.61(15.4) 200(292)
19 14 0.020(0.51) 0.060(1.52) 0.71(18.0) 270(400)
25 14 0.020(0.51) 0.060(1.52) 0.82(20.9) 405(597)
30 14 0.020(0.51) 0.060(1.52) 0.87(22.0) 520(770)
37 14 0.020(0.51) 0.080(2.03) 0.98(24.8) 610(1,144)
2 12 0.020(0.51) 0.045(1.14) 0.37(9.3) 85(124)
3 12 0.020(0.51) 0.045(1.14) 0.39(9.8) 110(163)
4 12 0.020(0.51) 0.045(1.14) 0.42(10.7) 140(205)
5 12 0.020(0.51) 0.045(1.14) 0.46(11.6) 170(246)
7 12 0.020(0.51) 0.045(1.14) 0.50(12.6) 220(325)
9 12 0.020(0.51) 0.060(1.52) 0.62(15.6) 295(438)
12 12 0.020(0.51) 0.060(1.52) 0.68(17.3) 380(560)
19 12 0.020(0.51) 0.060(1.52) 0.80(20.2) 570(846)
25 12 0.020(0.51) 0.080(2.03) 0.97(24.6) 775(1,153)
30 12 0.020(0.51) 0.080(2.03) 1.02(26.0) 910(1,350)
37 12 0.020(0.51) 0.080(2.03) 1.10(28.0) 1,095(1,627)
2 12 0.020(0.51) 0.045(1.14) 0.43(11.0) 120(176)
3 10 0.025(0.64) 0.045(1.14) 0.46(11.7) 160(238)
4 10 0.025(0.64) 0.045(1.14) 0.50(12.8) 205(302)
5 10 0.025(0.64) 0.060(1.52) 0.58(14.7) 265(392)
7 10 0.025(0.64) 0.060(1.52) 0.63(16.0) 350(517)
9 10 0.025(0.64) 0.060(1.52) 0.74(18.8) 440(654)
12 10 0.025(0.64) 0.060(1.52) 0.82(20.9) 570(843)
 
CERTIFIKATI

 

THHN PVC tray cable for direct burial

PAKIRANJE

 

VNTC tray cable for underground

Svitak

600V control cable for open air

Plastični kolut

600V control cable for indoor

Mali drveni kolut

PRIMJENA

 

VNTC tray cable for food processing plants
Automatizacija tvornice
VNTC tray cable for industrial automation
Procesna instrumentacija
TC-ER cable for motor control centers
Kontrolni sustavi za pročišćavanje vode
SPIS

 

VNTC tray cable for factory automation

BASF Ludwigshafen Verbund stranica

TC-ER cable for chemical plants

MWRA Deer Island postrojenje za pročišćavanje otpadnih voda

TC-ER cable for renewable energy plants

Siemens Electronic Works Tvornica Amberg

ZAŠTO ODABRATI NAS

 

30Godine iskustva
na jednom-usluzi

Dongguan Greater Wire & Cable Co., Ltd. je profesionalni inženjerski-proizvođač kabela u Kini, koji isporučuje certificirana rješenja električnih kabela za građevinske, industrijske, rudarske, energetske i infrastrukturne projekte širom svijeta.

S tvornicom od 30.000 m², 30 proizvodnih linija, iskusnim inženjerima i timom za strogu kontrolu kvalitete, nudimo pouzdane, sljedive i usklađene kabelske proizvode za međunarodne inženjerske primjene. Naši proizvodi podržani su certifikatima uključujući SAA, UL, cUL, VDE, TÜV, CE, CB, IEC, BPS i ISO.

Predani smo sigurnosti, kvaliteti, transparentnosti i dugoročnom-partnerstvu. Od inspekcije sirovina do testiranja gotovog proizvoda, svaka se serija pažljivo kontrolira kako bi se osigurala stabilna izvedba i pouzdana projektna uporaba.

Bolji kabel - Certificirana kvaliteta. Pouzdana opskrba. Inženjerska vrijednost.

buy 600V TC-ER tray cable
 
15K
Završeni projekti
150+
stručni kadar
15K
sretni klijenti
92+
nagrade i certifikati
POSTROJENA OPREMA

 

TC-ER cable wet dry rating
 
TC-ER cable Class 1 Div 2 use
 
TC-ER cable NEC 336 meaning
 
how to select VNTC tray cable
 
TC-ER cable direct burial requirements
 
TC-ER cable applications
 
GLOBALNI CERTIFIKATI

 

TC-ER cable exposed run rules

FOTOGRAFIJE KUPCA
 

THHN PVC tray cable meaning

MEĐUNARODNI PRIJEVOZ

 

01

Pomorski prijevoz

Nudimo pouzdana rješenja pomorskog prijevoza za-velike narudžbe. Vaša je roba sigurno zapakirana i otpremljena u kontejnere, čime se osigurava-isplativa dostava do luka širom svijeta.

02

Zračni prijevoz

Za bržu dostavu, naša usluga zračnog prijevoza osigurava da vaši proizvodi brzo stignu do međunarodnih odredišta, uz pažljivo rukovanje i potpuno praćenje na putu.

03

Međunarodni ekspres

Trebate hitne pošiljke? Naša međunarodna ekspresna usluga učinkovito isporučuje male do srednje narudžbe, pružajući uslugu od-do-vrata uz-praćenje u stvarnom vremenu za bezbrižnost.

TC cable vs TC-ER cable
ZADRUGA

 

Tražimo kooperativnog partnera za proširenje poslovanja.

600V TC-ER tray cable factory
600V TC-ER tray cable quote
TC-ER control cable cut to length
14 AWG 19 conductor VNTC tray cable 600V
TC-ER control cable for duct bank
VNTC tray cable for non ventilated tray
105C emergency overload tray cable
VNTC tray cable for cable tray
600V Type TC-ER UL 1277
Class 1 Div 2 Type TC-ER control cable
Kako surađivati ​​s nama?

Jednostavno podijelite svoje zahtjeve, primite naše profesionalno rješenje, potvrdite uzorke i uživajte u brzoj, pouzdanoj proizvodnji i isporuci diljem svijeta - raditi s nama je tako jednostavno.

Naša adresa

Zgrada 2, br. 40 Luxi 2nd Road, grad Liaobu, grad Dongguan, provincija Guangdong, Kina

Broj telefona

+86 136 6257 9592

+86 135 1078 4550

E-pošta

manager01@greaterwire.com

commercial 600V tray cable
FAQ

 

Koje su to prednostiClass 1 Div 2 VNTC nosač kabelaimati za opasne tvornice?
Ispunjava zahtjeve NEC-a za opasne lokacije klase I Divizije 2, s izolacijom otpornom na ulje-gas kako bi se izbjegli rizici paljenja u industrijskim okruženjima sa zapaljivom prašinom i parama.
Koje specifikacije potvrđuju da je to standardna UL 1277 kabelska polica 600V?
Cijela konstrukcija kabela, nazivni napon, izvedba TC-ER izloženog dijela i svojstvo usporavanja plamena strogo slijede pravila certificiranja kabela UL 1277 za industrijsko kontrolno ožičenje od 600 V.
Zašto je definiran kao ASTM B8 užetni kabel s bakrenom polici?
Svaka jezgra ima potpuno žarene bakrene užetane vodiče klase B proizvedene prema standardima ASTM B8, nudeći stabilnu vodljivost i izvrsnu izdržljivost na savijanje za dugo-trajno usmjeravanje.
Kako se ovaj ponaša kao profesionalni TC-ER upravljački kabel za instalaciju kanala?
Njegova okrugla kompaktna struktura uredno se uklapa u kabelske kanale i korita; TC-ER ocjena dopušta izloženi raspored unutar kanala bez dodatne zaštite cijevi za 3+ konfiguracije vodiča.

 

Hot Tags: 12 awg 600v tip tc-er oklopljeni kontrolni kabel pvc najlon pvc, Kina 12 awg 600v tip tc-er oklopljeni kontrolni kabel pvc najlon pvc proizvođači, dobavljači, tvornica

Send Inquiry